LINKS - Intumescent Paint : Flame Retardant Paint : Fire Varnish : Timbercoat : Wallcoat for Walls & Ceilings : Asbestos Encapsulating Coat : Home : Request Information : Fire Certificates |
INTUMESCENT
FIRE PROTECTION FIRE TESTING
APPLICATION QUALITY
ASSURANCE ENVIRONMENTAL
HEALTH & SAFETY Unit
B, Marlborough Court, Bennerley Road,
DESCRIPTION AND USE
Intumescent paint for bare or previously painted timber and timber derivative
surfaces where surface spread of flame or fire propogation need to be
controlled.
When exposed to a fire Thermoguard
Timbercoat expands to create a fire protective barrier, insulating the
timber surfaces from heat and oxygen.
TO SPECIFY
Simply state:
Prepare and apply
Thermoguard Timbercoat to Class 1/Class 0.
Apply Thermoguard Flame Retardant (insert chosen finish) according to
manufacturer's instructions.
Tested to
BS476 Part 7; Class
1 surface spread of flame.
BS476 Part 6; Fire
propogation.
Designated Class 0
in accordance with U.K.
Building Regulations.
FIRE CERTIFICATION
Thermoguard issue a
Certificate of Supply upon request for each project for Insurance,
Fire and Building Control Authority and Client Records.

FINISH AND COLOUR RANGE
Thermoguard Timbercoat
is overcoated with the following decorative finishes:
Thermoguard Flame Retardant:
Gloss.......................
BS 4800 + RAL.
Eggshell...................
BS 4800 + RAL.
Vinyl Matt................
BS 4800 + RAL.
Acrylic Eggshell........
BS 4800 + RAL
Anti-graffiti system..
Most BS4800 colours.
Metallic....................
Steel, gunmetal, rust,
silver, gold.
COVERAGE
Class 1 and Class 0:
Apply 2 coats of Thermoguard Timbercoat at 7m sq. per litre per coat.
Apply in 2 coats by brush or roller or spray.
Airless spray Graco 1500 or 5000 with 0.015" tip.
Pressure pot Devilbiss J.G.A 502 gun, 402-FF needle,
705 aircap, FF nozzle.
Thermoguard Timbercoat is manufactured under the principles of BS 5750/ISO
9000
COMPOSITION
Intumescent compounds.
Intumescent paint resin binders.
High opacity pigments.
Thermoguard Fire Varnish is
a low odour, water-based system, thus making it 'user and environmentally
friendly'
Blenheim Industrial Estate, Bulwell,
Nottingham. NG6 8UY
Tel: 0115-9764455 Fax: 0115-9764488
Technical Helpline: 01624-825115 Fax: 01624-825526
All materials and specifications are provided
in accordance with the terms and conditions of Thermoguard Ltd.
Refer to Health and Safety Data Sheet prior
to using this product.
| Click here for advice on fire doors and fire proof paints & coatings |